There are up to 3 tests which should be carried out to test that the Genius system has been installed correctly. This tests that the valves have been mounted correctly On the app, override one zone to 28°C for 1 hour. Ideally choose a room that has only 1 Radiator Valve. Check that the central heating pipe from the zone valve, pump or boiler gets hot. Wait 10 minutes! Now check the radiator in & out pipes and that each radiator is cold not hot! (Except for the overridden zone). Mark this on the commissioning form.Valve Seating Test
<Insert image of ESW with red dot on HUB>
The Communication Test
This tests that the Genius Radiator Valves can communicate with the Hub
Override all of the heating zones to 28°C.
Click on the 'My House' icon at the top left.
- Tap 'Override' at the bottom of the screen.
- Choose 'Select all'.
- Ensure the override temperature is 28°C and the override duration should be 1 hour.
- Check all the rooms receive the new set point temperature on the app. Each zone will have 'Set: 28'.
- You must wait 10 minutes!
- All of the valves will wake up on their own and get the message to go to 28ºC.
Make sure the radiator valves have received the message by pressing any of the three buttons to light up the screen. Each valve should read the Override temperature, i.e. 28ºC.
- This confirms all of the valves have good communication with the Genius Hub.
- The radiators do not need to warm up. The valves can take up to 30 minutes to react when newly installed as they learn how far the pin needs to be opened.
This tests that the Hot Water has been wired correctly Check the boiler fires as normal and the correct zone valve has opened or pump is running.The Hot Water Test