Troubleshooting step

After 5 minutes, go to the manifold which is used to divert water to the udnerfloor heating in the room in question. You should see that one (or more if the room is larger) of the actuators has started to open. This is often a line moving in the window on the side of the actuator, a flag which raises above the top of the actuator or the top of the actuator rises up. The manifold should also be allowing hot water to flow through the pipework.

Note: take care not to injure yourself on the hot pipework.

The pipework going to and from the room in question should not be heating up, which you should be able to tell be placing your hand near the pipework. The boiler should also be firing to provide hot water around the circuit.

1. If the boiler is firing and water is passing through the correct actuator(s): This means that the actuator(s) and wiring are working correctly.

2. If the boiler is firing but water is only passing through the wrong actuators: Ensure all of the other rooms are turned off and try again. If this is still the case then either the Electric Switch has been assigned to the incorrect room, or there is a problem with the wiring. A qualified electrician should be used to make any investigations or changes to the wiring.

3. If the boiler is firing but none of the actuators are open: There is a problem with either the actuators or the underfloor heating wiring centre, which should be investigated by a heating engineer. Either there is a faulty connection to the actuators or wiring centre, meaning that the wiring is incorrect and so cannot control the heating, or that the actuator(s) or wiring centre are faulty and so cannot open. One of these may need to be replaced.

4. The actuator(s) are open, but the boiler is not running and producing hot water: The wiring from the underfloor heating wiring centre to the boiler should be investigated and if fine there is a problem with the boiler as it should be running when the wiring centre calls for heat. A qualified electrician should be used to make any investigations or changes to the wiring.


Troubleshooting step


.

Doctor macro placeholder
MacroNamecancel-override

To finish the test, cancel the override for that zone by pressing the 'Stop Override' button at the bottom of the screen.

The override is no longer needed now that the test has been completed.

Doctor custom buttons
StartStepIndex2

...