Valve Seating Test

 This tests that the valves have been mounted correctly

  1. On the app, override one zone to 28°C for 1 hour. Ideally choose a room that has only 1 Radiator Valve. 

    1. Click on the zone to override.
    2. Change the mode icon at the top-right to the Override symbol (3 arrows).
    3. Ensure the override temperature is 28°C and the override duration should be 1 hour.
  2. Check that the Receiver Unit is active:
    1. A Single Channel Receiver shows a green light.


      Pagebreak
    2. Hold down the Heating button on the the Dual Channel Receiver (the light at the top-left with turn green for 2 seconds).
    3. An Electric Switch shows a red light next to 'HUB'.
  3. Check the boiler fires as normal and the correct zone valve has opened or pump has come on.
  4. Check that the central heating pipe from the zone valve, pump or boiler gets hot.

  5. Wait 10 minutes!

  6. Now check the radiator in & out pipes and that each radiator is cold not hot! (Except for the overridden zone).

    Info

    This confirms all the valves are properly seated on the radiators, and they can turn the radiators off

Pagebreak


The Communication Test

This tests that the Genius Radiator Valves can communicate with the Hub 

...

 This tests that the Hot Water has been wired correctly

Note

Only complete if hot water control is installed


  1. Override the Hot Water on the app for 1 hour.
    1. Click on the hot water zone on the app.
    2. Change the mode icon at the top-right to the Override symbol (3 arrows).
      1. If the hot water is an On/Off zone, select the override setting as ON.
      2. If the hot water is a temperature zone, select a much temperature higher than the current measured temperature.
    3. Ensure the duration is 1 hour.
  2. Check the relay on dual/single channel receiver is active.
    1. A Single Channel Receiver shows a green light.
    2. Hold down the Hot Water button on the the Dual Channel Receiver (the light at the top-left with turn green for 2 seconds).
    3. An Electric Switch shows a red light next to 'HUB'.
  3. Check the boiler fires as normal and the correct zone valve has opened or pump is running.

    Info
    • This confirms This confirms the Genius Hub has control over the hot water.
    • If the boiler does not fire, the Cylinder Stat may be stopping the boiler as the Hot Water tank is already up to temperature. To test this increase the cylinder stat temperature temporarily, to check the zone valve opens and boiler fires. The cylinder stat must be returned to what is appropriate for the property after the test has been completed.


...